Optimal Capacitor Placement in Voltage- Dependent Distribution Networks Using Hybrid PSO–MILP: Case Study: Murang’a 11 kV Distribution Feeder, Kenya

dc.contributor.authorKarobia, Pauline Njeri
dc.contributor.authorMuriithi, Christopher M.
dc.contributor.authorNgoo, Livingstone
dc.date.accessioned2026-11-25T06:45:54Z
dc.date.issued2026-10-13
dc.description.abstractThis paper presents a hybrid optimization methodology for optimal capacitor placement in radial distribution networks with voltage-dependent loads. The proposed approach employs Particle Swarm Optimization (PSO) for location selection and Mixed Integer Linear Programming (MILP) for discrete sizing, simultaneously minimising active power losses, voltage deviation and equipment investment cost. The methodology incorporates the ZIP (constant impedance–constant current–constant power) load model and is validated against ETAP commercial software. Application to the Murang’a 11 kV distribution feeder in Kenya (253 buses, 69 km, 2,434 kW peak demand) identified a 450 kvar capacitor at Bus 115 as the optimal solution, reducing medium-voltage violations from 125to 11 buses (91.2% reduction) while improving the power factor from 96.06% to99.16%. The algorithm achieved convergence with an average execution time of42.3 seconds on a standard desktop environment. When benchmarked against a standalone Genetic Algorithm, the hybrid PSO–MILP achieved superior solution quality (mean annual cost of USD 93,061 vs. USD 93,287), 38% faster convergence, and less than half the solution dispersion (standard deviation of USD 124.8 vs. USD241.6). Statistical validation through 30 independent PSO runs confirmed algorithmic robustness with a coefficient of variation of 0.13%. The study quantifies the impact of voltage-dependent loads on capacitor performance and demonstrates the voltage compliance versus loss minimization trade-off characteristic of highR/X ratio feeders.
dc.identifier.doi10.64470/elene.2026.43
dc.identifier.urihttps://repository.mut.ac.ke/handle/123456789/7240
dc.language.isoen
dc.publisherElectrical Engineering and Energy |
dc.subjectCapacitor placement
dc.subjectParticle Swarm Optimization
dc.subjectMixed Integer Linear Programming
dc.subjectVoltage-dependent loads
dc.subjectZIP load model
dc.subjectRadial distribution network
dc.titleOptimal Capacitor Placement in Voltage- Dependent Distribution Networks Using Hybrid PSO–MILP: Case Study: Murang’a 11 kV Distribution Feeder, Kenya
dc.typeArticle
oaire.citation.endPage20
oaire.citation.issue1
oaire.citation.startPage1
oaire.citation.titleElectrical Engineering and Energy |
oaire.citation.volume6

Files

Original bundle

Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
Optimal Capacitor Placement in Voltage-.pdf
Size:
965.11 KB
Format:
Adobe Portable Document Format

License bundle

Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
license.txt
Size:
2.06 KB
Format:
Item-specific license agreed upon to submission
Description: