Article 2026 MUT Institutional Repository

Optimal Sizing and Techno-Economic Analysis of Battery Energy Storage System for Peak Shaving and Voltage Profile Improvement on a Rural Distribution Network

Loading...
Thumbnail Image

Journal Title

Journal ISSN

Volume Title

Publisher

Electrical Engineering and Energy

Abstract

Distribution networks are increasingly strained by peak load demands and voltage regulation problems. This paper benchmarks Particle Swarm Optimization, Boda-Boda Optimization, and Adaptive Boda-Boda Optimization Algorithm with Fuzzy Logic (ABBOA-Fuzzy) to size and site Battery Energy Storage System (BESS) as a Non-Wires Alternative for rural 11kV feeder support. Baseline analysis of the feeder indicated a peak load of 99.6%, and a voltage drop to 0.936 p.u. The optimization process demonstrated the superiority of the ABBOA-Fuzzy algorithm, which converged faster. The optimized solution guided the selection of a commercially available 400kW/1200kWh BESS which reduced peak demand by 15.5% and raised the minimum voltage to 0.952 p.u. A 15-yeartechno-economic analysis using the System Advisor Model, accounting for battery degradation confirmed the economic viability with a Net Present Value of $43,643and an Internal Rate of Return of 15.54%. The study recommends this framework for utility BESS planning.

Description

Keywords

Battery Energy Storage System (BESS), Net Present Value (NPV), Non-Wires Alternative (NWA), System Advisor Model (SAM

Publication Details

Journal
Electrical Engineering and Energy
Volume
5
Issue
1
Pages
17 –36

Endorsement

Review

Supplemented By

Referenced By